| Specification |
| Electrical
|
| Ratio Range |
Auto-Ranging, 0.8000 to
1500.0:1 |
| Accuracy |
Ratio<10 to 1: +/-0.2% of Reading,
Ratio<=10 to1000 to 1: +/-0.1% of Reading, Ratio>1000
to 1: +/-0.2% of Reading |
| Excitation Signal |
PT/VT Mode: 44Vrms maximum, CT Mode:
0 to 1A Auto Level, 0.1 to 5Vrms |
| Excitation Current Display |
Range: 0 to 1000mA, Accuracy: +/-2%
of Reading +/-2mA |
| Excitation Frequency |
70 Hz |
| Display |
LCD Character, 20 x 2, Large format,
LED Backlight, day/night visible |
| Measurement Method |
In accordance with ANSI/IEEE C57.12.90 |
| Power Source |
Dual operation; rechargeable NiCD
battery & 115 /230V, 50/60Hz |
| Batteries |
12V, 5 x 2 NiCD packs, 1300mAH, Panasonic
P-130SCR or equivalent |
| Charging Time |
Up to 10 hours continuous operation,
May be used while recharging. Low battery LCD indication. |
| Line Fuse |
115V: 1.0A, 5 x 20mm, slow acting,
230V: 0.5A, 5 x 20mm, slow acting, |
| Displayed Measurements |
True ratio; RMS excitation current,
polarity |
| Displayed Messages |
Incorrect lead connections, H/X reversal
(accidental step-up misconnection); Short (excess excitation
current); Open circuit; Circuit continuity & low battery |
| Mechanical |
| Connections |
Cannon XLR connectors and large color-coded
industrial clips |
| Leads |
15ft, H x X color-coded, in carrying
bag |
| Display |
Dual line alpha-numeric 3.875 x 0.875
" with contrast adjustment and backlight |
| Operating Temperature |
32°C to 122°F (0 to 50 °C),
0 to 90% RH ( without condensation) |
| Dimensions |
13 x 12 x 6 " (330 x 305 x 152
mm) |
| Weight |
14lb (6.4Kg) |