| Specification |
| Electrical
|
| VT/PT Ratio Range |
Auto-Ranging, 0.8000 to
8000.0:1 |
| CT Ratio Range |
Auto-Ranging, 0.8000 to 8000 |
| Accuracy |
Ratio<10 to 1: +/-0.2% of Reading,
Ratio<=10 to1000 to 1: +/-0.1% of Reading, Ratio>1000
to 1: +/-0.2% of Reading, Ratio 5000 to 8000: +/-0.25% of Reading |
| Excitation Signal |
PT/VT Mode: 32Vrms maximum, CT Mode:
0 to 1A Auto Level, 0.1 to 5Vrms |
| Excitation Current Display |
Range: 0 to 1000mA, Accuracy: +/-2%
of Reading +/-2mA |
| Excitation Frequency |
70 Hz |
| Display |
LCD 16 Character, 2 line, Large format,
LED Backlight, day/night visible |
| Measurement Method |
In accordance with IEEE Std C57.12.90
- 2006 |
| Languages Supported |
English, Spanish, Franch,
Italian, German, Portuguese |
| Power Source |
Two 12V, 1650mAH rechargeable battery
packs |
| Battery Life |
UP to 10 hrs of continuous operation,
low battery indication |
| Charging Time |
<4 hrs to full charge |
| Data Storage |
10,000 tests |
| Date / Time |
Battery-backed, Real-time clock |
| Communication |
USB 2.0 compliant, optically isolated
115.2 KB |
| Software |
DataView analysis software included |
| Mechanical |
| Connections |
XLR connectors |
| Leads |
15ft (4.6m), H & X shielded with
color-coded alligator clips |
| Enclosure |
Heavy duty Polypropylene case, UL
94 V0 rated |
| Protection |
IP40 (Instrument lid open, IP53 (Instrument
lid closed) |
| Dimensions |
10.7 x 9.76 x 5.12" (272 x 248
x 130mm) |
| Weight |
8.1 lbs (3.7 Kg) |
| Safety |
EN 61010-1; 50V CAT IV; Pollution
Degree 2 |